  • Output Ratings:
  • Voltage: Up to 20 V
  • Current: Up to ±3 A
  • Power: 20 W
  • Programming Accuracy (at 23°C ± 5°C after 30 minute warm-up. Applies from min. to max. program):
  • Voltage, 20 V range: 0.025% + 1.8 mV
  • Voltage, 6 V range: 0.025% + 600 µV
  • Current, 3 A and 1 A ranges: 0.04% + 300 µA
  • Current, 300 mA range: 0.03% + 150 µA
  • Output Programming Speed:
  • Output voltage can change in 10 µs or at 100 kHz into a resistive load
  • Measurement Accuracy (at 23°C ± 5°C):
  • Voltage, 20 V range: 0.025% + 1.2 mV*
  • Current, 3 A range: 0.03% + 250 µA*
  • Current, 100 mA range: 0.025% + 10 µA*
  • Current 10 µA range: 0.025% + 8 nA
  • *Agilent patented feature: Seamless Measurement Ranging